• MTU-Diesel-Gen-Sets_1139_image278.png

CM32C Inline 5580 kWe to 7840 kWe

Each generator set has been designed to meet World bank (WB) emission certification stage 2.

Details and Information: CM32C Inline 5580 kWe to 7840 kWe

Categories: , Tag:

Description

GENERATOR SET SPECIFICATIONS:
Minimum Rating: 5580 kWe
Maximum Rating: 7840 kWe
Emissions/Fuel Strategy: (WB) Cert stage 1 and 2
Voltage: 3000 to 13800 Volts
Frequency At Speed: 50 Hz @ 750 / 60 Hz @ 720
Duty Cycle: Prime, Continuous
Ready To Accept Loads: (Preheated/Vented) 40 s
Normal Ramp: Up To 100% Load 95 s
Emergency Ramp: Up 10% To 100% Load 35 s
Genset Efficiency: Up To 46.70%

ENGINE SPECIFICATIONS:
Engine Model: CM32C V-Type, 4-stroke-engine
Bore: 12.6 in
Stroke: 18.11 in
Aspiration: Turbocharged-aftercooled
Engine Rating Range: 6000 – 8000 kW
Configuration: 12,16 cylinder
Fuel Type: Diesel oil / heavy fuel oil (HFO) / crude oil
Swept Volume: 2258.0 in?
Mean Effective Pressure: Up To 326.0 psi

GENERATOR SET DIMENSIONS:
Length – Minimum 421.0 in
Length – Maximum 478.0 in
Width – Minimum 139.0 in
Width – Maximum 139.0 in
Height – Minimum 183.0 in
Height – Maximum 183.0 in
Dry Weight – Genset (minimum) 251327.0 lb
Dry Weight – Genset (maximum) 317465.0 lb